| Product Model |
LFL1.333 |
| Brand |
Siemens |
| Product Type |
Burner Control (for gas/oil/dual-fuel forced draft burners) |
| Series |
02 Series |
| Article Number |
BPZ:LFL1.333 |
| Application |
Medium-to-high capacity burners; multistage/modulating burners (intermittent operation); stationary air heaters |
| Flame Supervision |
Supports UV detectors (QRA2/QRA4/QRA10) and ionization probe |
| Mains Voltage |
AC 230 V (-15%/+10%); AC 100-110 V (-15%/+10%) (order with “-110 V” suffix) |
| Mains Frequency |
50-60 Hz (±6%) |
| Power Consumption |
Approx. 3.5 VA |
| Built-in Fuse |
T6.3H250V (DIN EN 60127) |
| External Primary Fuse (Si) |
Max. 10 A (slow) |
| Weight |
Approx. 1000 g |
| Dimensions (L×W×H) |
123 mm × 103 mm × 37 mm (based on LFL1 series & AGM plug-in base) |
| Protection Rating |
IP40 (when built-in, excluding terminal base) |
| Safety Class |
Class II |
| Operating Temperature Range |
-20…+60 °C |
| Storage/Transport Temperature |
-20…+60 °C |
| Relative Humidity |
<95% RH (non-condensing) |
| Max. Installation Altitude |
2000 m above sea level |
| Key Timing Parameters (50 Hz) |
t1 (prepurge): 31 s; TSA (ignition safety time): 3 s; t3 (preignition): 6 s; t6 (postpurge): 18 s; t8 (startup sequence): 69 s |
| Permissible Detector Cable Length |
UV detector (normal cable): max. 100 m; UV detector (shielded): max. 200 m; Ionization probe (normal): max. 80 m; Ionization probe (shielded): max. 140 m |
| Control Terminal Load |
Max. 4 A continuous (20 A peaks/20 ms) for terminals 3,6,7,9-11,15-20 |
| Required Switching Capacity |
1 A AC 250 V (between terminals 4&5, 4&12, 4&14) |
| Certifications |
CE (complies with 2014/35/EC, 2009/142/EC, EU 2016/426, 2014/30/EC); EAC; ISO 9001:2015; ISO 14001:2015; OHSAS 18001:2007; China RoHS |
| Mechanical Design |
Plug-in design; impact-proof/heat-resistant black plastic housing; lockout reset button with fault indicator |
| Climatic Classification |
Operation: DIN EN 60721-3-3 Class 3K3; Storage: Class 1K3; Transport: Class 2K3 |