| Electrical connection |
Motor: screw terminal 95…120 mm²/AWG 3…250 kcmil
Line side: screw terminal 95 mm²/AWG 2/0…250 kcmil
Control: removable screw terminals 0.5…1.5 mm²/AWG 20…AWG 16 |
| Connector type |
RJ45 (on the remote graphic terminal) for Modbus serial
RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP |
| Data format |
8 bits, configurable odd, even or no parity |
| Type of polarization |
No impedance |
| Exchange mode |
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP |
| Number of addresses |
1…247 for Modbus serial |
| Method of access |
Slave Modbus TCP |
| Supply |
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection |
| Local signalling |
3 LEDs (dual colour) for embedded communication status
4 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
3 LEDs for local diagnostic |
| Width |
345 mm |
| height |
1250 mm |
| Depth |
375 mm |
| Net weight |
87 kg |
| analogue input number |
3 |
| Analogue input type |
AI1, AI2, AI3 software-configurable voltage: 0…10 V DC, impedance: 31.5 kOhm, resolution 12 bits
AI1, AI2, AI3 software-configurable current: 0…20 mA, impedance: 250 Ohm, resolution 12 bits
AI2 voltage analog input: – 10…10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
| Discrete input number |
8 |
| Discrete input type |
DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) |
| Input compatibility |
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68
STOA, STOB: discrete input level 1 PLC conforming to IEC 61131-2
DI1…DI6: discrete input level 1 PLC conforming to IEC 61131-2 |
| Discrete input logic |
Positive logic (source) (DI1…DI8), < 5 V (state 0), > 11 V (state 1)
Negative logic (sink) (DI1…DI8), > 16 V (state 0), < 10 V (state 1) |
| analogue output number |
2 |
| Analogue output type |
Software-configurable voltage AQ1, AQ2: 0…10 V DC impedance 470 Ohm, resolution 10 bits
Software-configurable current AQ1, AQ2: 0…20 mA, resolution 10 bits
Software-configurable current DQ-, DQ+: 30 V DC
Software-configurable current DQ-, DQ+: 100 mA |
| Sampling duration |
5 ms +/- 1 ms (DI5, DI6) – discrete input
5 ms +/- 0.1 ms (AI1, AI2, AI3) – analog input
10 ms +/- 1 ms (AO1) – analog output
2 ms +/- 0.5 ms (DI1…DI4) – discrete input |
| Accuracy |
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input |
| Linearity error |
AO1, AO2: +/- 0.2 % for analog output
AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input |
| Relay output number |
3 |
| Relay output type |
Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles |
| Refresh time |
Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
| Minimum switching current |
Relay output R1, R2, R3: 5 mA at 24 V DC |
| Maximum switching current |
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC
Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC |
| Isolation |
Between power and control terminals |
| Maximum output frequency |
500 kHz |
| Maximum input current |
156.2 A |
| Variable speed drive application selection |
Building – HVAC compressor centrifugal |
| Motor power range AC-3 |
55…100 kW at 380…440 V 3 phases |
| Quantity per set |
1 |
| enclosure mounting |
Wall mounted |