| MAIN SPECIFICATIONS |
| Analogue Input Number |
100…277 V AC 45…65 Hz
100…300 V DC
173…480 V AC 45…65 Hz |
| Contacts Type And Composition |
1 A
5 A |
| Control Type |
1P + N
3P
3P + N |
| Display Type |
backlit LCD |
| Measurement Accuracy |
current 0.3 % 0.5…6 A
current 0.5 % 0.1…1.2 A
voltage 0.3 % 50…330 V
voltage 0.3 % 80…570 V |
| Product Or Component Type |
power meter |
| Communication Port Protocol |
– |
| Device Short Name |
PM3210 |
| EAN13 |
3606480481598 |
| Mounting Support |
DIN rail |
| Power Quality Analysis |
up to the 15th harmonic |
| Range |
PowerLogic |
| Range Name |
PM3000 series |
| Type Of Measurement |
active and reactive power
apparent power
current
energy
frequency
power factor
total current harmonic distortion THD (I)
total voltage harmonic distortion THD (U)
voltage |
| COMPLEMENTARY |
| Analogue Input Type |
current 0…1 A
current 0…5 A |
| Analogue Output Number |
backlit LCD |
| Communication Gateway |
128 x 96 pixels |
| Display Resolution |
128 x 96 pixels |
| Output Voltage |
current 0…1 A
current 0…5 A |
| Product Name |
PowerLogic PM3000 |
| Time Delay |
current 0.3 % 0.5…6 A
current 0.5 % 0.1…1.2 A
voltage 0.3 % 50…330 V
voltage 0.3 % 80…570 V |
| [In] Rated Current |
1 A
5 A |
| Accuracy Class |
class 0.5S active energy conforming to IEC 62053-22
class 1 active energy conforming to IEC 62053-21
class 2 reactive energy conforming to IEC 62053-23
class C active energy conforming to EN 50470-3 |
| Communication Port Support |
– |
| Compatibility Code |
PM3210 |
| Data Recording |
5 alarms
min/max of instantaneous values
time stamping |
| Depth |
70 mm |
| Device Application |
multi-tariff
power monitoring
sub billing |
| Frequency Measurement Range |
45-65 Hz |
| Height |
95 mm |