| Standards |
IEC 61131-2 |
| product certifications |
CE
UKCA
RCM
EAC
cULus
cULus HazLoc |
| Resistance to electrostatic discharge |
8 kV in air conforming to IEC 61000-4-2
4 kV on contact conforming to IEC 61000-4-2 |
| Resistance to electromagnetic fields |
10 V/m 80 MHz…1 GHz conforming to IEC 61000-4-3
3 V/m 1.4 GHz…2 GHz conforming to IEC 61000-4-3
1 V/m 2 GHz…3 GHz conforming to IEC 61000-4-3 |
| Resistance to magnetic fields |
30 A/m conforming to IEC 61000-4-8 |
| Resistance to fast transients |
1 kV (I/O) conforming to IEC 61000-4-4 |
| Resistance to conducted disturbances |
10 V 0.15…80 MHz conforming to IEC 61000-4-6
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
| Electromagnetic emission |
Radiated emissions – test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011
Radiated emissions – test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to IEC 55011 |
| Immunity to microbreaks |
10 ms |
| Ambient air temperature for operation |
-10…55 °C horizontal installation
-10…35 °C vertical installation |
| Ambient air temperature for storage |
-25…70 °C |
| Relative humidity |
10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage) |
| IP degree of protection |
IP20 |
| Pollution degree |
2 |
| Operating altitude |
0…2000 m |
| Storage altitude |
0…3000 m |
| Vibration resistance |
3.5 mm at 5…8.4 Hz on DIN rail
3 gn at 8.4…150 Hz on DIN rail |
| Shock resistance |
15 gn for 11 ms |