| Standards |
IEC 61131-2 |
| Product Certifications |
cULus
CE
UKCA
RCM
EAC
cULus HazLoc |
| Resistance to electrostatic discharge |
8 kV in air IEC 61000-4-2
4 kV on contact IEC 61000-4-2 |
| Resistance to electromagnetic fields |
9.14 V/m (10 V/m) 80 MHz…1 GHz IEC 61000-4-3
2.74 V/m (3 V/m) 1.4 GHz…2 GHz IEC 61000-4-3
0.91 V/m (1 V/m) 2 GHz…3 GHz IEC 61000-4-3 |
| Resistance to magnetic fields |
98.43 A/m (30 A/m) 50/60 Hz IEC 61000-4-8 |
| Resistance to fast transients |
1 kV I/OIEC 61000-4-4 |
| Surge withstand |
1 kV I/O common mode IEC 61000-4-5 DC |
| Resistance to conducted disturbances |
10 V 0.15…80 MHz IEC 61000-4-6
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL) |
| Electromagnetic emission |
Radiated emissions 40 dBμV/m QP class A 10 m)30…230 MHz IEC 55011
Radiated emissions 47 dBμV/m QP class A 10 m)230…1000 MHz IEC 55011 |
| Ambient Air Temperature for Operation |
14…95 °F (-10…35 °C) vertical installation
14…131 °F (-10…55 °C) horizontal installation |
| Ambient Air Temperature for Storage |
-13…158 °F (-25…70 °C) |
| Relative humidity |
10…95 %, without condensation in operation)
10…95 %, without condensation in storage) |
| IP degree of protection |
IP20 with protective cover in place |
| Pollution degree |
2 |
| Operating altitude |
0…6561.68 ft (0…2000 m) |
| Storage altitude |
0.00…9842.52 ft (0…3000 m) |
| Vibration resistance |
3.5 mm 5…8.4 Hz DIN rail
3 gn 8.4…150 Hz DIN rail
3.5 mm 5…8.4 Hz panel
3 gn 8.4…150 Hz panel |
| Shock resistance |
15 gn 11 ms |