| Number of analogue outputs |
2 |
| Mains voltage |
480 V |
| Integrated breaking resistance |
No |
| Max. output voltage |
932 V |
| Internal dynamic brake resistors |
115 Ohm |
| DC bus overvoltage trip |
810V DC @ 480V |
| DC nominal bus voltage |
648V DC @ 480V |
| Brake IGBT |
Brake IGBT installed |
| Internal communication module |
No communication module |
| Fuse current rating |
40 A @ 650V DC |
| Input voltage rating |
480V AC, 3-phase, 60 Hz |
| Displacement power factor |
0.98 across speed range |
| Output current, continuous |
22 A @ 650V DC |
| Output current, 1 min |
24.2 A @ 650V DC |
| Output current, 3 sec |
33 A @ 650V DC |
| Circuit breaker current rating, max |
80 A @ 480V AC, 3-phase |
| Motor circuit protector current rating, max |
30 A @ 480V AC, 3-phase |
| Logic control ride-thru |
0.25 seconds, drive not running |
| Brake resistor |
No internal brake resistor |
| Input current rating |
23.3 A @ 650V DC |
| Rated power rating |
15 Hp @ 650V DC, normal duty |
| Documentation |
English documentation |
| Carrier frequency |
Drive rating: 4 kHz, settings: 2, 4, 6, 8, 10 kHz (6 kHz is for V/Hz operation only) |
| AC input overvoltage trip |
600V AC @ 480V (six pulse, 3-phase) |
| Input power rating |
16.6 kVA @ 480V AC, 3-phase |
| Electronic motor overload protection |
Class 10 motor overload protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126 (A)(2). UL 508C file E59272 |
| Dual element time delay fuse current rating |
25…50 A @ 480V AC, 3-phase |
| Non-time delay fuse current rating |
25…80 A @ 480V AC, 3-phase |
| Heat sink thermistor |
Monitored by microprocessor overtemperature trip |
| Drive to motor power ratio, max |
The drive to motor rating cannot exceed a 2:1 ratio |
| Stop modes |
Multiple programmable stop modes including – Ramp, Coast, and Current Limit |
| Acceleration/deceleration |
Independently programmable accel and decel times adjustable from 0 to 6553.5 in 0.1 second increments |
| Number of digital inputs |
6 |
| Number of digital outputs |
2 |
| Number of analogue inputs |
3 |
| Motor voltage, nom |
460V @ 380…400V drive rating, 480V nominal line voltage |
| Human interface model |
No HIM (no blank plastic inserted) |
| Additional configuration |
Phase II control |
| Max. output frequency |
400 Hz |
| Line voltage, nom |
480V @ 380…400V drive rating, 460V nominal motor voltage |
| Mains frequency |
60 Hz |
| Internal EMC filtering |
With EMC filter & common mode choke |
| Watt loss |
389 W @ 480V AC, 15 Hp normal duty, 10 Hp heavy duty |
| Feedback option |
Future use |
| Drive full power range |
460…528V @ 380…400V drive rating, 460V nominal motor voltage |
| Drive operating range |
325…528V @ 380…400V drive rating, 460V nominal motor voltage |
| Torque regulation |
Torque regulation – without feedback: ±5%, 600 rad/sec bandwidth |
| Enclosure type |
IP20/NEMA/UL Type 1 |
| Output current rating |
22 amps, 15 Hp normal duty, 10 Hp heavy duty, frame 1 |
| Control options |
Phase II control, expanded cassette |
| Drive overcurrent trip |
Software current limit: 105% of motor rated to 200% of drive rated current |
| Efficiency |
97.5% at rated amps, nominal line volts |
| Speed control |
Speed regulation – without feedback: 0.1% of base speed across 120:1 speed range, 120:1 operating range, 50 rad/sec bandwidth |
| Current limit capability |
Independent motoring and regenerative power limits programmable to 800% of rated output current |
| Selectable motor control |
Field oriented control with and without a feedback device and permanent magnet motor control |
| Input phases |
Six-pulse, 3-phase input provides full rating for all drives, single-phase operation provides 50% of rated current |
| Control method |
Induction motor and brushless motor: sine coded PWM with programmable carrier frequency, indirect self organized, field-oriented control, current-regulated, ratings apply to all drives, refer to the PowerFlex 700S Phase ll control reference manual, public |
| Number of phases output |
3 |
| Number of phases input |
3 |
| Relative symmetric net voltage tolerance |
10 % |
| Input frequency, max |
400 Hz |
| Output frequency range |
0 Hz |
| DC bus undervoltage trip |
Adjustable |
| Output voltage range |
0 to rated motor voltage |
| Power ride-thru |
15 milliseconds at full load |
| S-curve time |
Adjustable 0.5…4.0 seconds |
| Short circuit trip |
Phase-to-phase on drive output |
| Ground fault trip |
Phase-to-ground on drive output |
| Control logic noise immunity |
Showering arc transients upto 1500V peak |
| Line transients |
Up to 6000 volts peak per IEEE C62.41-1991 |
| Intermittent overload |
110% overload capability for up to 1 minute, 150% overload capability for up to 3 seconds |
| Short circuit current, max |
Using recommended fuse or circuit breaker type: maximum short circuit current rating to match specified fuse/circuit breaker capability ≤200000 Amps |
| Encoder voltage supply |
5V DC or 12V DC 320 mA/channel, 5V DC minimum high state voltage state of 0.4V DC, 12V DC minimum high state voltage of 7.0V DC, maximum low state voltage of 0.4V DC |