| Product Model |
MVI69E-MBTCP |
| Brand |
ProSoft Technology |
| Product Type |
Modbus TCP/IP Enhanced Communication Module |
| Compatible Controllers |
CompactLogix series (1769 I/O bus, version 16+; MicroLogix 1500 not supported) |
| Physical Form Factor |
Standard 1769 Single-slot module |
| Power Requirement |
Max 500 mA @ 5 VDC |
| Ethernet Port |
1×10/100 Mbps Auto-negotiating Ethernet Port (for diagnostic & application data) |
| Supported Connections |
Up to 20 Modbus Client connections; Up to 20 Modbus Server connections (10 MBAP, 10 Encapsulated Modbus) |
| Max Data Capacity |
Up to 10,000 words of data |
| Supported Modbus Functions |
1 (Read Coil Status), 2 (Read Input Status), 3 (Read Holding Registers), 4 (Read Input Registers), 5 (Force Single Coil), 6 (Preset Single Holding Register), 8 (Diagnostics, Slave Only), 15 (Force Multiple Coils), 16 (Preset Multiple Holding Registers), 17 (Report Slave ID, Slave Only), 22 (Mask Write Holding Register, Slave Only), 23 (Read/Write Holding Registers, Slave Only) |
| Floating Point Support |
Enron, Daniel style, and other configurable implementations |
| Integration Features |
Add-on Profile, Add-on Instruction (creates UDTs), configuration backed up in CompactLogix ACD file |
| Operating Temperature |
32°F to 140°F (0°C to 60°C) |
| Storage Temperature |
-40°F to 185°F (-40°C to 85°C) |
| Relative Humidity |
5% to 95% (non-condensing) |
| LED Indicators |
Application Status, Backplane Connectivity Status |
| Key Role |
Acts as co-processor to reduce PLC scan time impact; suitable for SCADA & field device interface |