| Item |
Specification |
| Power supply |
Supply voltage |
Single/three phase 200~240V -10%~+10%;
Three phase 380~480V -10%~+10%; |
| Frequency |
48-62Hz; |
| Max. imbalance |
3% ; |
| Motor output |
Output voltage |
Three phase 0-100% of supply voltage |
| Output frequency |
V/F : 0-400Hz , VVC+: 0-200Hz; |
|
IO
board
control
terminals |
Input |
5 digital inputs (1 supports pulse input, pulse range: 20Hz~5kHz);
1 analog input, both can receive voltage or current signals. |
| Output |
1 relay output;
1 analog input (only supports current output). |
| Power supply |
1 +10V, max current output 10mA;
1 +24V, max current output 200mA; |
| Communication |
RS+, RS-, max baud rate 38400bit/s; |
| Display |
8 segments, 5 numeric displays |
Display frequency, warnings, status and so on; |
| Indicator |
Light FWD, REV, HZ, A, RPM display various status of the drive; |
| Data read-outs |
Frequency setting, output frequency, feedback value, output current, DC link voltage, output voltage, output power, input terminals state, output terminals state, analogue input , analogue output, 1-10 fault records and accumulated working time etc.; |
| Environment |
Enclosure |
IP20; |
| Ambient temperature |
-10℃~50℃, derating use when over 40℃; |
| Humidity |
5%-85% (95% without condensation); |
| Vibration test |
1.14g; |
| Max. altitude above sea level |
1000m, derating use when more than 1000 meters; |
| Motor cable length |
Shield cable: 5 meters; Unshield cable: 50 meters; |
| Others |
DC choke |
≥18.5kW Built-in |
| Braking unit |
≥1.5kW Built-in |